Performance of Ejector Cooling System with Thermal Pumping Effect Using R141b and R365mfc
Applied Thermal Engineering(2009)
Abstract
The ejector cooling system (ECS) is suitable for solar cooling application due to its simple design and low cost. An ECS using a multi-function generator (ECS/MFG) as a thermal pumping device without rotating machines for refrigerant circulation has been designed and tested. The experiment of an ECS/MFG operating at full-cycle while using R141b has shown that the COPo can reach 0.225 and cooling capacity of 0.75kW at generator temperature 90°C, condenser temperature 37°C, and evaporator temperature 8.5°C. The present study also redesigned the ejector for working fluid R365mfc in order to replace R141b. This study has shown that R365mfc can replace R141b as the working fluid of ECS/MFG at no payoff of system performance as long as the ejector design is optimized.
MoreTranslated text
Key words
Ejector cooling system,Ejector,R365mfc,R141b
PDF
View via Publisher
AI Read Science
Must-Reading Tree
Example

Generate MRT to find the research sequence of this paper
Data Disclaimer
The page data are from open Internet sources, cooperative publishers and automatic analysis results through AI technology. We do not make any commitments and guarantees for the validity, accuracy, correctness, reliability, completeness and timeliness of the page data. If you have any questions, please contact us by email: report@aminer.cn